uaGate SI

OPC UA Server Gateway with MQTT Connectivity for S7 Controllers

uaGate SI is a compact gateway for industrial use providing convenient and secure data connectivity without the need for a PC. It integrates data from SIMATIC S7-300, S7-400, S7-1200 and S7-1500 PLCs via OPC UA into higher-level management software such as ERP, MES or SCADA of new or existing installations. Using the MQTT Publisher functionality, these data can be integrated into IoT cloud applications.

OPC Competence Brochure

Overview

Access to Siemens PLC Data from OPC UA Applications

  • Access to SIMATIC S7-300, S7-400, S7-1200 and S7-1500 controllers
  • Integration of higher-level management systems like ERP, MES or SCADA using integrated OPC UA Server providing open, platform-independent and market-proven communication
  • Easy local and global access to field data and routing through firewalls
  • Especially dedicated to retrofit upgrades, thus protecting former investments
  • No need for software updates, operating system patches and PC updates resulting in years of failure-free operation
  • No PLC programming or dedicated PC required

Optimized for Siemens Integration

  • Direct symbol import from SIMATIC STEP 7 and TIA Portal projects, thus avoiding any PLC programming
  • Easy setup of OPC UA Server requiring only a few steps for accessing Siemens PLC data
  • Web-based interface for gateway configuration

Industry-proven Security

  • Physically separated interfaces and separate configuration rights for OT and IT networks preventing intrusions
  • Supporting security standards as SSL/TLS and X.509 certificates
  • OPC UA compliant data encryption and user authentification
  • Security supported for MQTT communication with private and public clouds

Technical Details

HardwareProcessorAltera Cyclone V SoC with Dual-core ARM Cortex-A9
 Connectors2 x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
 Status LEDsPWR (power supply), RUN (running), ERR (error), SYS (configuration)
 Dimensions (H x W x D)100 mm x 22.5 mm x 105 mm
 Power Supply18 VDC ... 32 VDC, SELV/PELV supply mandatory Typically 200 mA, maximum 1 A at switch-on
 Operating Temperature, Horizontal DIN Rail Installation-40 °C .. 50 °C (0 mm minimum distance)
-40 °C .. 55 °C (22.5 mm minimum distance)
 Operating Temperature, Vertical DIN Rail Installation-40 °C .. 35 °C (0 mm minimum distance)
-40 °C .. 40 °C (22.5 mm minimum distance)
 Storage Temperature-40 °C .. 85 °C
 Relative Humidity10 % ... 90 %, non-condensing
 WeightAbout 0.2 kg
 MountingDIN Rail (35 mm)
 HousingPhoenix Contact ME MAX
 Protection ClassIP20
SoftwareProtocolsSIMATIC S7 , OPC UA (Server, 20,000 items in total), MQTT (Publisher, 1,000 topics)
 Supported ControllersSiemens S7-300, S7-400, S7-1200, S7-1500
 Supported Engineering ToolsSIMATIC STEP 7, TIA Portal V13, V13 SP1, V14, V14 SP1
ConformityEmissionEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55011, Group 1, Class A 
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55022, Class A 
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-4 
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A), 
VCCI Class A Information Technology Equipment 2002
 ImmunityEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-2
CertificationsCE, FCC, RoHS

Downloads

Get access to our Downloads

You need a MySofting account to be able to access our Downloads. Register here or log in if you already have one.

Order Numbers

GAA-DX-145111dataFEED uaGate SI

 

Scope of Delivery

HardwaredataFEED uaGate SI
SoftwareTool for configuration over integrated web interface
DocumentationQuick Startup Guide (printed documentation)

Videos

uaGate SI Confugration (German)