uaGate SI

OPC UA Server Gateway with MQTT Support for SIMATIC S7 Controllers

uaGate SI makes data integration easier than ever before.

The gateway supports the connection of SIMATIC S7-300, S7-400, S7-1200 and S7-1500 controllers from Siemens and uses the OPC UA standard for a simple and secure data integration of new and existing plants in higher-level management systems, such as ERP, MES or SCADA systems.

In addition, uaGate SI also offers MQTT Publisher functionality, enabling direct integration of PLC data into private or public IoT cloud applications on the IT side. The generic MQTT implementation supports the use of a large number of different cloud providers. Similar to the OPC UA standard, MQTT also supports various security mechanisms such as encrypted connections, certificates and user authentication, thus contributing to a high level of data security.

With this functionality, uaGate SI is a compact, secure, future-oriented and proven gateway for data integration.

Access to Siemens PLC Data from OPC UA Applications

  • Access to SIMATIC S7-300, S7-400, S7-1200 and S7-1500 controllers
  • Support of optimized data blocks in SIMATIC S7-1200 and S7-1500 controllers
  • Integration of higher-level management systems like ERP, MES or SCADA using integrated OPC UA Server providing open, platform-independent and market-proven communication
  • Easy local and global access to field data and routing through firewalls
  • Especially dedicated to retrofit upgrades, thus protecting former investments
  • No need for software updates, operating system patches and PC updates resulting in years of failure-free operation
  • No PLC programming or dedicated PC required

Optimized for Siemens Integration

  • Symbolic name import from Siemens TIA Portal and SIMATIC STEP 7 projects
  • Namespace configuration by browsing of SIMATIC S7 1200/1500 variables
  • Easy setup of OPC UA Server requiring only a few steps for accessing Siemens PLC data
  • Web interface for gateway configuration

Industry-proven Security

  • Physically separated interfaces and separate configuration rights for OT and IT networks preventing intrusions
  • Supporting security standards as SSL/TLS and X.509 certificates
  • OPC UA compliant data encryption and user authentification
  • Security supported for MQTT communication with private and public clouds

How-to Videos

uaGate SI Configuration (German)

How-To connect uaGate SI with OPC UA Client

How-To configure uaGate SI with Simatic S7 controller and optimized access.

How-To configure uaGate SI with Siemens SIMATIC-S7 controller

Downloads

Technical Details

HardwareProcessorAltera Cyclone V SoC with Dual-core ARM Cortex-A9
 Connectors2 x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
 Status LEDsPWR (power supply), RUN (running), ERR (error), SYS (configuration)
 Dimensions (H x W x D)100 mm x 22.5 mm x 105 mm
 Power Supply18 VDC ... 32 VDC, SELV/PELV supply mandatory Typically 200 mA, maximum 1 A at switch-on
 Operating Temperature, Horizontal DIN Rail Installation-40 °C .. 50 °C (0 mm minimum distance)
-40 °C .. 55 °C (22.5 mm minimum distance)
 Operating Temperature, Vertical DIN Rail Installation-40 °C .. 35 °C (0 mm minimum distance)
-40 °C .. 40 °C (22.5 mm minimum distance)
 Storage Temperature-40 °C .. 85 °C
 Relative Humidity10 % ... 90 %, non-condensing
 WeightAbout 0.2 kg
 MountingDIN Rail (35 mm)
 HousingPhoenix Contact ME MAX
 Protection ClassIP20
SoftwareProtocolsSIMATIC S7 , OPC UA (Server, 20,000 items in total), MQTT (Publisher, 1,000 topics)
 Supported ControllersSiemens SIMATIC S7-300/400, SIMATIC S7-1200/1500 (including optimized block access) and Siemens-compatible PLC like VIPA controllers
 Supported Engineering ToolsSIMATIC STEP 7, TIA-Portal V13/V14/V15 including Service Packs
ConformityEmissionEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55011, Group 1, Class A 
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55022, Class A 
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-4 
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A), 
VCCI Class A Information Technology Equipment 2002
 ImmunityEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-2
CertificationsCE, FCC, RoHS
Open Source License Declarationhttp://opensource.softing.com/IA/dataFEEDUAGateway/V1/

Order Numbers

GAA-DX-145111dataFEED uaGate SI

 

Scope of Delivery

HardwaredataFEED uaGate SI
SoftwareTool for configuration over integrated web interface
DocumentationQuick Startup Guide (printed documentation)